ELECTRICAL TRANSFORMERS
Most of the electronic circuits used in
Circuitstoday.com have different applications of the transformer.
Therefore, it is important to know the working principle, construction
and types of transformers used in different analog circuits.
Transformer – Working Principle
A transformer can be defined as a static
device which helps in the transformation of electric power in one
circuit to electric power of the same frequency in another circuit. The
voltage can be raised or lowered in a circuit, but with a proportional
increase or decrease in the current ratings.
The main principle of operation of a
transformer is mutual inductance between two circuits which is linked by
a common magnetic flux. A basic transformer consists of two coils that
are electrically separate and inductive, but are magnetically linked
through a path of reluctance. The working principle of the transformer
can be understood from the figure below.
As shown above the transformer has
primary and secondary windings. The core laminations are joined in the
form of strips in between the strips you can see that there are some
narrow gaps right through the cross-section of the core. These staggered
joints are said to be ‘imbricated’. Both the coils have high mutual
inductance. A mutual electro-motive force is induced in the transformer
from the alternating flux that is set up in the laminated core, due to
the coil that is connected to a source of alternating voltage. Most of
the alternating flux developed by this coil is linked with the other
coil and thus produces the mutual induced electro-motive force. The so
produced electro-motive force can be explained with the help of
Faraday’s laws of Electromagnetic Induction as
e=M*dI/dt
If the second coil circuit is closed, a
current flows in it and thus electrical energy is transferred
magnetically from the first to the second coil.
The alternating current supply is given
to the first coil and hence it can be called as the primary winding. The
energy is drawn out from the second coil and thus can be called as the
secondary winding.
In short, a transformer carries the operations shown below:
- Transfer of electric power from one circuit to another.
- Transfer of electric power without any change in frequency.
- Transfer with the principle of electromagnetic induction.
- The two electrical circuits are linked by mutual induction.
Transformer Construction
For the simple construction of a
transformer, you must need two coils having mutual inductance and a
laminated steel core. The two coils are insulated from each other and
from the steel core. The device will also need some suitable container
for the assembled core and windings, a medium with which the core and
its windings from its container can be insulated.
In order to insulate and to bring out
the terminals of the winding from the tank, apt bushings that are made
from either porcelain or capacitor type must be used.
In all transformers that are used
commercially, the core is made out of transformer sheet steel
laminations assembled to provide a continuous magnetic path with minimum
of air-gap included. The steel should have high permeability and low
hysteresis loss. For this to happen, the steel should be made of high
silicon content and must also be heat treated. By effectively laminating
the core, the eddy-current losses can be reduced. The lamination can be
done with the help of a light coat of core plate varnish or lay an
oxide layer on the surface. For a frequency of 50 Hertz, the thickness
of the lamination varies from 0.35mm to 0.5mm for a frequency of 25
Hertz.
Types of Transformers
The types of transformers differ in the
manner in which the primary and secondary coils are provided around the
laminated steel core. According to the design, transformers can be
classified into two:
1. Core- Type Transformer
In core-type transformer, the windings
are given to a considerable part of the core. The coils used for this
transformer are form-wound and are of cylindrical type. Such a type of
transformer can be applicable for small sized and large sized
transformers. In the small sized type, the core will be rectangular in
shape and the coils used are cylindrical. The figure below shows the
large sized type. You can see that the round or cylindrical coils are
wound in such a way as to fit over a cruciform core section. In the case
of circular cylindrical coils, they have a fair advantage of having
good mechanical strength. The cylindrical coils will have different
layers and each layer will be insulated from the other with the help of
materials like paper, cloth, micarta board and so on. The general
arrangement of the core-type transformer with respect to the core is
shown below. Both low-voltage (LV) and high voltage (HV) windings are
shown.
The low voltage windings are placed
nearer to the core as it is the easiest to insulate. The effective core
area of the transformer can be reduced with the use of laminations and
insulation.
2. Shell-Type Transformer
In shell-type transformers the core
surrounds a considerable portion of the windings. The comparison is
shown in the figure below.
The coils are form-wound but are multi
layer disc type usually wound in the form of pancakes. Paper is used to
insulate the different layers of the multi-layer discs. The whole
winding consists of discs stacked with insulation spaces between the
coils. These insulation spaces form the horizontal cooling and
insulating ducts. Such a transformer may have the shape of a simple
rectangle or may also have a distributed form. Both designs are shown in
the figure below:
A strong rigid mechanical bracing must
be given to the cores and coils of the transformers. This will help in
minimizing the movement of the device and also prevents the device from
getting any insulation damage. A transformer with good bracing will not
produce any humming noise during its working and will also reduce
vibration.
A special housing platform must be
provided for transformers. Usually, the device is placed in
tightly-fitted sheet-metal tanks filled with special insulating oil.
This oil is needed to circulate through the device and cool the coils.
It is also responsible for providing the additional insulation for the
device when it is left in the air.
There may be cases when the smooth tank
surface will not be able to provide the needed cooling area. In such
cases, the sides of the tank are corrugated or assembled with radiators
on the sides of the device. The oil used for cooling purpose must be
absolutely free from alkalis, sulphur and most importantly moisture.
Even a small amount of moistures in the oil will cause a significant
change in the insulating property of the device, as it lessens the
dielectric strength of the oil to a great extent. Mathematically
speaking, the presence of about 8 parts of water in 1 million reduces
the insulating quality of the oil to a value that is not considered
standard for use. Thus, the tanks are protected by sealing them
air-tight in smaller units. When large transformers are used, the air
tight method is practically difficult to implement. In such cases,
chambers are provided for the oil to expand and contract as its
temperature increases and decreases. These breathers form a barrier and
resists the atmospheric moisture from contact with oil. Special care
must also be taken to avoid sledging. Sledging occurs when oil
decomposes due to over exposure to oxygen during heating. It results in
the formation of large deposits of dark and heavy matter that clogs the
cooling ducts in the transformer.
The quality, durability and handling of
these insulating materials decide the life of the transformer. All the
transformer leads are brought out of their cases through suitable
bushings. There are many designs of these, their size and construction
depending on the voltage of the leads. Porcelain bushings may be used to
insulate the leads, for transformers that are used in moderate
voltages. Oil-filled or capacitive-type bushings are used for high
voltage transformers.
The selection between the core and shell
type is made by comparing the cost because similar characteristics can
be obtained from both types. Most manufacturers prefer to use shell-type
transformers for high-voltage applications or for multi-winding design.
When compared to a core type, the shell type has a longer mean length
of coil turn. Other parameters that are compared for the selection of
transformer type are voltage rating, kilo-volt ampere rating, weight,
insulation stress, heat distribution and so on.
Transformers can also be classified
according to the type of cooling employed. The different types according
to these classifications are:
1. Oil Filled Self-Cooled Type
Oil filled self cooled type uses small
and medium-sized distribution transformers. The assembled windings and
core of such transformers are mounted in a welded, oil-tight steel tanks
provided with a steel cover. The tank is filled with purified, high
quality insulating oil as soon as the core is put back at its proper
place. The oil helps in transferring the heat from the core and the
windings to the case from where it is radiated out to the surroundings.
For smaller sized transformers the tanks are usually smooth surfaced,
but for large size transformers a greater heat radiation area is needed,
and that too without disturbing the cubical capacity of the tank. This
is achieved by frequently corrugating the cases. Still larger sizes are
provided with radiation or pipes.
2. Oil Filled Water Cooled Type
This type is used for much more economic
construction of large transformers, as the above told self cooled
method is very expensive. The same method is used here as well- the
windings and the core are immersed in the oil. The only difference is
that a cooling coil is mounted near the surface of the oil, through
which cold water keeps circulating. This water carries the heat from the
device. This design is usually implemented on transformers that are
used in high voltage transmission lines. The biggest advantage of such a
design is that such transformers do not require housing other than
their own. This reduces the costs by a huge amount. Another advantage is
that the maintenance and inspection of this type is only needed once or
twice in a year.
3. Air Blast Type
This type is used for transformers that
use voltages below 25,000 volts. The transformer is housed in a thin
sheet metal box open at both ends through which air is blown from the
bottom to the top.
E.M.F Equation of a Transformer
Let,
NA = Number of turns in primary
NB = Number of turns in secondary
Ømax = Maximum flux in the core in webers = Bmax X A
f = Frequency of alternating current input in hertz (HZ)
As shown in figure above, the core flux increases from its zero value to maximum value Ømax in one quarter of the cycle , that is in ¼ frequency second.
Therefore, average rate of change of flux = Ømax/ ¼ f = 4f ØmaxWb/s
Now, rate of change of flux per turn means induced electro motive force in volts.
Therefore, average electro-motive force induced/turn = 4f Ømaxvolt
If flux Ø varies sinusoidally, then r.m.s value of induced e.m.f is obtained by multiplying the average value with form factor.
Form Factor = r.m.s. value/average value = 1.11
Therefore, r.m.s value of e.m.f/turn = 1.11 X 4f Ømax = 4.44f Ømax
Now, r.m.s value of induced e.m.f in the whole of primary winding
= (induced e.m.f./turn) X Number of primary turns
Therefore,
EA = 4.44f NAØmax = 4.44fNABmA
Similarly, r.m.s value of induced e.m.f in secondary is
EB = 4.44f NB Ømax = 4.44fNBBmA
In an ideal transformer on no load,
VA = EA and VB = EB , where VB is the terminal voltage
Voltage Transformation Ratio (K)
From the above equations we get
EB/ EA = VB/ VA = NB/NA = K
This constant K is known as voltage transformation ratio.
(1) If NB>NA , that is K>1 , then transformer is called step-up transformer.
(2) If NB<1, that is K<1 , then transformer is known as step-down transformer.
Again for an ideal transformer,
Input VA = output VA
VAIA = VBIB
Or, IB/IA = VA/VB = 1/K
Hence, currents are in the inverse ratio of the (voltage) transformation ratio.
No comments:
Post a Comment